|

If the PCB is sealed with solid sealant, how to determine the creepage distance and clearance?

functional insulation as well as other insulation exists on circuit boards. Typically, the surface environment of a circuit board is determined to be either Pollution degree 3 or pollution degree 2.
If the circuit board is mounted in an electrical box and sealed with a solid sealant, the sealing will look as follows:

What should be the pollution degree of the functional insulation between the copper tracks on the PCB and between the energized parts on the component?
Here, the functional insulation is located inside the solid sealant and there is no contact between the path of the functional insulation and the outside air. According to the definition of electrical clearance, it can be assumed that there is no electrical clearance here. At the same time, the creepage distance is defined along the surface of the insulation, and obviously, there is no surface here either.
It may be argued that there is still a gap between the solid sealant and the PCB material, and that an clearance and creepage distance can be formed, but it is a pollution degree 1. This view is more conservative, because even if a gap is formed, it is not a continuous gap.
At the same time, the pictures show that this solid state sealant fills so well that it is essentially impossible to create a gap. The manufacturer also indicates that there is a vacuuming procedure prior to filling the solid state sealant. When we evaluate this type of structure, we can have some control over the material and specification of the solid state sealant, as well as some control over the filling process.
There may also be reinforced insulation internally, as there are isolation measures between the 220-240V circuit portion and the SELV circuit, which are judged by the same rules for clearance and creepage distances as functional insulation.

Similar Posts

  • 第3項 「定格電圧」の定義の見方

    定格電圧:メーカーによってアプライアンスに割り当てられた電圧。 通常、この電圧は、製品設計時の対象市場の国の標準商用電圧です。ターゲット市場が決定したら、メーカーはターゲット市場の要件に従って製品を設計する必要があります。商用電源がAC220Vの国で使用することを目的として、定格電圧AC100V(電源入力電圧)の製品を設計することはできません。同時に、ほとんどの国では主電源電圧が定義されているため、ここでの定格電圧値は別の値になります。国際電気標準会議は、すべての国のプラグと主電源電圧に関する情報をリストした Web ページを提供しています。 https://iectest.iec.ch/world-plugs。参考までに IEC 60335-1 規格では、製品に電力を供給すること、または製品が動作状態にあることを必要とするすべてのテストは定格電圧に基づいています。定格電圧の選択が間違っている場合は、すべてのテストを繰り返す必要があります。研究室は、テストを実行する前に定格電圧を決定する必要があります。 IEC 60335-1 では、定格電圧を設定すべき定格電圧の値や範囲は規定されていませんが、実際には定格電圧の範囲は第 1 項の最初の段落で参考として示されており、これは定格電圧を設定するものではありません。単相の場合は 250 V、三相およびその他の電源タイプの機器の場合は 480 V を超えます。一般に、定格電圧はこの範囲を超えることはありません。各国が IEC 60335-1 規格に基づいて独自の偏差を追加しており、これらの偏差により一般に定格電圧要件が増加することに注意することが重要です。たとえば、日本では 100V、英国では 240V、中国では 220V です。 A クラス I バッテリ充電器の PDSH 2235 には、定格供給特性 3N~ および定格電圧 400V がマークされているという決定があります。 このバッテリ充電器は、250 V 以下の指定定格電圧制限に関して IEC 60335-2-29:2016 の範囲内にありますか?決定回答:規格の範囲によれば、定格電圧 400V(3N~)の充電器は IEC 60335-2-29 の対象外となります。

  • Clause 3 – How to understand the definition of “thermostat”

    thermostat: temperature-sensing device, the operating temperature of which may be either fixed or adjustable and which during normal operation keeps the temperature of the controlled part between certain limits by automatically opening and closing a circuit. The thermostat itself does not control the temperature, the thermostat senses the temperature and controls the temperature by switching…

  • Clause 3 – How to understand the definition of “electronic component”

    electronic component: part in which conduction is achieved principally by electrons moving through a vacuum, gas or semiconductor.NOTE Neon indicators are not considered to be electronic components. Early vacuum tubes were components that allowed electrons to conduct in a vacuum and were the core components of old radios and televisions.Electrons move through specific gases, colliding…

  • 第3項 「特別低圧」の定義の見方

    特別低電圧:機器内の電源から供給される電圧であって、機器が定格電圧で供給されている場合に、導体間および導体とアース間が50Vを超えない電圧 EU 低電圧指令の定義によれば、低電圧の範囲は AC で 50 ~ 1000V、DC で 75 ~ 1500V です。ちなみに、ほとんどの国ではこの電圧値に応じて高電圧と低電圧を分けています。したがって、範囲の上限を超える電圧は高電圧となり、範囲の下限を下回る電圧は超低電圧となります。この規格における定義では、DC と AC は区別されません。ここで注意していただきたいのは、電圧名は電圧値に応じて定義されているだけであり、低電圧回路の特定の部分を定義するものではありません。電圧は相対的なものであるため、電圧を測定する場合、電圧は両端間で測定する必要があります。つまり、電圧には基準点が必要であるため、規格ではワイヤ間およびワイヤとアース間の電圧について言及しています。 一般家庭用アルカリ電池の出力電圧、一般家庭用電化製品の制御基板上の変圧器以降の低圧回路やRC降圧回路の動作電圧など、いずれも特別低電圧と定義できるもの. 下図のようにR1とC1で降圧機能が完成しますので、R1とC1以降の回路は特別低圧回路と定義できます。

  • 第 3 項 – 「沿面距離」の定義の理解方法

    沿面距離: 2 つの導電性部品間、または導電性部品とアクセス可能な表面間の絶縁体表面に沿った最短距離。 電荷は空気中を指向性を持って伝播し、電流を形成します。これがクリアランスの意味です。完全に絶縁された材料はないため、実際には電荷は絶縁材料自体を通って伝播する可能性もあります。通常のA4印刷用紙の両面と厚さ2mmのトレッドゴム材の両面に電位の異なる2つの電極を印加した場合、2つの電極間に形成される電流の差は非常に大きくなります。電荷は、絶縁材料の表面に沿って方向性を持って伝播することもあります。異なる材料の表面における電荷伝播の影響も異なります。絶縁材の表面に他の物質(汚染物質)が付着している場合、電荷伝播の影響も異なります。電荷が絶縁材料の表面に沿って伝播して感電を引き起こすのを防ぐために、沿面距離の定義と要件が作成されます。絶縁材料本体を通した電荷の伝播により、第 29 条の最初の段落に記載されている固体絶縁要件が生成されます。第 29.2 条には、沿面距離の要件が示されています。 沿面距離の定義は IEC 60664-1:2020 規格に基づいています。沿面距離を説明する必要があるため、IEC 60664-1:2020規格の図4から図14までの図を示す必要があります。ここで、読者は「X mm」をどのように決定するかを慎重に検討する必要があります。沿面距離を形成する経路上に溝がある場合、橋溝の状況が発生します。私は個人的に、ブリッジの主な原因は溝への汚染物質の堆積であると考えています。これらの汚染物質は主に粉塵であり、湿った粉塵は導電性が高くなります。したがって、規格の原文をコピーすると、次の 3 つの前提条件があります。– 溝を横切る距離が指定された幅 X (表 1 を参照) より小さい場合、沿面距離は溝を直接横切って測定され、溝の輪郭は考慮されません (図 4 を参照)– 溝を横切る距離が指定された幅 X 以上である場合 (表 1 を参照)、沿面距離は溝の輪郭に沿って測定されます (図 5 を参照)。– 凹部は、指定された幅 X に等しい長さを持ち、最も不利な位置に配置された絶縁リンクで橋渡しされていると想定されます (図 6 を参照)。– 相互に異なる位置を想定できる部品間で測定される隙間と沿面距離は、これらの部品が最も不利な位置にあるときに測定されます。 条件: 検討中のパスには、幅 X mm 未満の任意の深さの平行または収束側面の溝が含まれています。ルール: クリアランスと沿面距離は、図に示すように溝を直接横切って測定されます。 クリアランス沿面距離 条件: 検討中のパスに、任意の深さで X mm 以上の平行な側面の溝が含まれているルール:クリアランスとは「見通し」の距離です。沿面経路は溝の輪郭に従います。 クリアランス沿面距離 条件:…

  • 第3項 「第3種建築物」の定義の見方

    クラスⅢ構造:感電に対する保護が安全特別低電圧に依存しており、安全特別低電圧以上の電圧が発生しない機器の一部注記 SELV での供給に加えて、基礎絶縁が必要な場合があります。 8.1.4を参照してください。注 2 機器の主要部分が SELV で動作し、取り外し可能な電源ユニットと一緒に納入される場合、機器のこの主要部分はクラス I 機器またはクラス II 機器のクラス III 構造とみなされます。 アプライアンスはプラグイン可能なアダプター (保護接地なし) によって電力を供給され、アダプターとアプライアンスは一緒にユーザーに配送されます。アダプターとアプライアンスは合わせてクラス II アプライアンスとして判断されます。アダプターはクラス II であるため、これによって感電に対する保護のクラスが決まります。ただし、機器 – ファンのみはクラス III 構造、つまりクラス II 機器内のクラス III 構造です。 もちろん、スイッチ電源 PCB が機器に組み込まれており、このスイッチ電源 PCB が SELV 回路を提供できるという別の状況もあります。そして、SELV回路部分はクラスII構造となっております。 Of course, there is another situation, that is, a switch power supply PCB is embedded in the appliance, and…