Clause 3 – How to Understand the Definition of “all-pole disconnection”

all-pole disconnection: disconnection of both supply conductors by a single initiating action or, for multi-phase appliances, disconnection of all supply conductors by a single initiating action
NOTE For multi-phase appliances, the neutral conductor is not considered to be a supply conductor.

Single-phase power: An AC power system composed of one live wire and one neutral wire.
Three-phase power: An AC power system composed of three live wires, with the same frequency and a phase difference of 120 degrees between each.

Single-phase power has two poles, which are the live wire/pole and the neutral wire/pole, generally, when we refer to multi-phase power, it is typically Three-phase power. Three-phase power has two type of connection such ass Star connection (Y connection) and Delta connection (Δ connection).

Star connection (Y connection): In a Star connection (Y connection), one end of each of the three load supply leads is joined to form a common neutral point. The other ends are connected to the three live wires, respectively.
Delta connection (Δ connection): The three load supply power leads are connected end-to-end, forming a closed loop, with the connection points respectively connected to the three live wires.
The supply conductors mentioned in the standard refer to the live wire and neutral wire in single-phase power, as well as all conductors in three-phase power except the neutral wire in a star connection. Each conductor is defined as a pole or supply conductor.

A disconnection is considered all-pole disconnection if a single action simultaneously disconnects both the live and neutral wires in a single-phase power system, or all supply conductors in a three-phase power system.
The purpose of defining all-pole disconnection is to provide protection against electric shock. In single-phase systems, both neutral and live conductors are considered live parts. Similarly, in three-phase systems, all live conductors are considered live parts. As shown in the below pictures, it shows the three-phase power system and single-phase power system appliance, the temperature limiter shown in pictures is an all-pole disconnection.

Electric tankless water heater electrical diagram
3 phase Electric tankless water heater electrical diagram

Below pictures show a thermal cut-out/ thermostat, you can find the all-pole disconnection diagram in its rating label.

Immersion Thermostat & safety thermal cut-out in plumbing&heating water container

The bipolar thermal cut-out used in the kettle is shown in the figure below.

Dual Pole Thermal cut-out for Water boiler
Electric Water Dry Burn Overheat Protector, Bipolar Disconnection

The diagram below shows a three-pole thermal overload relay, which is an example of an all-pole disconnection device.

Thermal Overload Relay Working Principle Diagram
3-poles thermal overload relay

The wire connection diagram and the picture of thermal protective devices used in water heaters with container are shown in pictures below:

thermostat with temperature Adjustable one pole and 2-pole disconnection hand reset-1
thermostat with temperature Adjustable one pole and 2-pole disconnection hand reset
thermostat with temperature Adjustable one pole and 2-pole disconnection hand reset diagram

thermostat with temperature Adjustable one pole and 2-pole disconnection hand reset diagram.

Similar Posts

  • ข้อ 3 – จะเข้าใจคำจำกัดความของ “ฉนวนเสริม” ได้อย่างไร

    จากหมายเหตุ สามารถทดสอบฉนวนเสริมและฉนวนพื้นฐานได้ทีละชิ้น ซึ่งหมายความว่าฉนวนเสริมและฉนวนพื้นฐานสามารถแยกแยะและแยกออกจากกันได้อย่างง่ายดาย ในทำนองเดียวกัน หากฉนวนประกอบด้วยหลายชั้นหรือหลายฉนวนที่ไม่สามารถแยกและแยกแยะได้ง่าย แต่เทียบเท่ากับฉนวนสองชั้นตามผลของฉนวนจริง ก็สามารถนิยามได้ว่าเป็นฉนวนเสริม นอกจากนี้ หากเป็นเพียงชั้นเดียวหรือฉนวนอิเล็กทริกเดียว ผลของฉนวนจะเทียบเท่ากับฉนวนสองชั้น ก็ยังสามารถกำหนดเป็นฉนวนเสริมได้ดังแสดงในสองภาพด้านล่าง ภาพซ้ายเป็นภาพด้านหลังตู้เย็น แผงวงจรด้านในสามารถมองเห็นได้ผ่านตะแกรงโลหะในภาพด้านซ้าย และภาพภายในคือภาพด้านขวา มีส่วนที่มีกระแสไฟฟ้าอยู่บน PCB และผู้ใช้สามารถสัมผัสกระจังหน้าได้ อากาศระหว่างช่องว่างของกระจังหน้าและชิ้นส่วนที่มีไฟฟ้าบนแผงวงจรอาจทำให้เกิดวงจรนำไฟฟ้าได้ ดังนั้นระยะนี้สามารถกำหนดเป็นระยะห่างด้วยฉนวนเสริมได้ เพราะการกวาดล้างและ nbsp; และ nbsp;ประกอบด้วยห่วงอากาศ ห่วงอากาศไม่สามารถแยกออกได้ และเราไม่รู้ด้วยซ้ำว่าจะแบ่งอากาศนี้ออกเป็นหลายส่วนที่ไหน ที่นี่ต้องสังเกตสองประเด็น ถ้าตะแกรงโลหะไม่ได้ต่อสายดิน อากาศระหว่างตะแกรงและชิ้นส่วนที่มีไฟฟ้าในแผงวงจรต้องเป็นไปตามข้อกำหนดของฉนวนเสริม (ตามข้อกำหนดในข้อ 8.2 สำหรับเครื่องใช้ไฟฟ้าประเภท II) ถ้าตะแกรงโลหะต่อสายดิน ดังนั้นอากาศระหว่างตะแกรงและชิ้นส่วนที่มีกระแสไฟฟ้าในแผงวงจรจะต้องเป็นไปตามข้อกำหนดของฉนวนพื้นฐานเท่านั้น เนื่องจากฉนวนพื้นฐานพร้อมสายดินเป็นอุปกรณ์ Class I ที่มีมาตรการป้องกันสองชั้น และผู้ใช้สามารถสัมผัสชิ้นส่วนโลหะที่ต่อสายดินได้ ปั๊มจุ่มที่แสดงด้านล่างมีโพลมอเตอร์สีเทาอยู่ภายใน โดยมีขดลวดหุ้มด้วยฉนวนสีเหลือง เพื่อป้องกันความเสียหายจากน้ำ สเตเตอร์ของมอเตอร์ทั้งหมดจึงถูกห่อด้วยอีพอกซีเรซิน หลังจากที่พันขดลวดแล้ว จะไม่สามารถทดสอบฉนวนพื้นฐานและฉนวนเสริมได้อย่างมีประสิทธิภาพ ก่อนที่จะเทอีพอกซีเรซิน ฉนวนสีเหลืองถือได้ว่าเป็นฉนวนพื้นฐาน และอีพอกซีเรซินถือได้ว่าเป็นฉนวนเสริม อย่างไรก็ตาม เมื่อเทอีพอกซีเรซินลงในตัวเรือนปั๊ม มันจะยึดติดกับวัสดุฉนวนสีเหลืองอย่างแน่นหนา และไม่สามารถแยกวัสดุทั้งสองออกเพื่อการประเมินได้ เช่น การประเมินการทดสอบความแข็งแรงทางไฟฟ้า ดังนั้นฉนวนเสริมจึงถูกสร้างขึ้นตั้งแต่ขดลวดปั๊มไปจนถึงพื้นผิวอีพอกซีเรซินที่สามารถเข้าถึงได้จากภายนอก…

  • Clause 3 – How to understand the definition of “protective device”

    protective device: device, the operation of which prevents a hazardous situation under abnormal operation conditions The standard emphasizes “abnormal operation” here. Only devices that operate under “abnormal operation” conditions can be defined as protective devices. Therefore, there are many types of protective devices, including overheating protection devices, overcurrent protection devices, and overpressure protection devices. Overheating…

  • A question about whether the second part of clause 21.2 needs to be tested.

    We know that clause 29.3.2 and clause 21.2 are two separate clauses and they are not very much related, which means that the product being assessed needs to fulfill both clauses if applicable.A reinforced insulation system consisting of three separate layers of insulating material or what could be considered a double insulation system, Each layer…

  • ข้อ 3 – จะเข้าใจคำจำกัดความของ “การกวาดล้าง” ได้อย่างไร

    พื้นผิวที่เข้าถึงได้การกวาดล้างเป็นแนวคิดที่สำคัญมาก เพื่อให้เข้าใจถึงการกวาดล้าง เราต้องพูดอีกครั้งว่าไม่มีสารใดเป็นฉนวนโดยสมบูรณ์ และอากาศก็สามารถนำไฟฟ้าได้เช่นกัน เมื่อแรงดันไฟฟ้าสูงมาก กระแสไฟฟ้าจะถูกนำผ่านอากาศ ฟ้าผ่าระหว่างเกิดพายุฝนฟ้าคะนองเป็นตัวอย่างทั่วไปของฟ้าผ่าที่ผ่านอากาศ แรงดันไฟฟ้าของฟ้าผ่าสูงมาก จึงสามารถทะลุผ่านอากาศส่วนที่ยาวมากได้ ทำให้อากาศส่วนนี้เป็นสื่อกระแสไฟฟ้า ในเครื่องใช้ไฟฟ้าในครัวเรือนถึงแม้แรงดันไฟฟ้าจะต่ำมาก แต่ก็มีอากาศอยู่ในผลิตภัณฑ์เป็นจำนวนมาก และกระแสไฟจะถูกนำผ่านอากาศด้วย เมื่อแรงดันไฟฟ้าเพิ่มขึ้น ระยะทางที่แรงดันไฟฟ้าอาจทะลุผ่านอากาศก็จะนานขึ้นเช่นกัน สิ่งนี้ทำให้เกิดแนวคิดเรื่องการกวาดล้าง สำหรับคำอธิบายโดยละเอียดเกี่ยวกับการกวาดล้าง โปรดดู IEC 60664-1 (การประสานงานของฉนวนสำหรับอุปกรณ์ภายในระบบไฟฟ้าแรงต่ำ – ส่วนที่ 1: หลักการ ข้อกำหนด และการทดสอบ)ฉันคิดว่ารูปภาพต่อไปนี้สามารถอธิบายเส้นทางการกวาดล้างทางไฟฟ้าได้ดี ช่องว่างอาจเกิดขึ้นระหว่างอิเล็กโทรดสองตัวที่มีแรงดันไฟฟ้าต่างกัน หรือระหว่างชิ้นส่วนที่มีไฟฟ้ากับมือของผู้ใช้ผลิตภัณฑ์ไฟฟ้า คุณเพียงแค่ต้องจินตนาการว่าอิเล็กโทรดทั้งสองในภาพด้านบนเป็นวัตถุอื่น เมื่อเราอธิบายฉนวนพื้นฐานและฉนวนตามการใช้งาน เราได้ให้ภาพถ่ายจริงบางส่วนเพื่ออธิบายตัวอย่างการกวาดล้างและการเคลื่อนตัว รูปที่ 11 – ตัวอย่างระยะห่างในมาตรฐาน IEC 60335-1 เป็นตัวอย่างง่ายๆ จากตัวเลขนี้ เราสามารถคิดถึงคุณลักษณะพื้นฐานของอุปกรณ์คลาส II โครงสร้างคลาส II อุปกรณ์คลาส I และการสร้างคลาส I คีย์ 1 ชิ้นส่วนโลหะที่ขุดขึ้นมาและเข้าถึงได้2 กล่องหุ้ม3 ชิ้นส่วนโลหะที่ต่อลงดินที่เข้าถึงได้4 ชิ้นส่วนโลหะที่ขุดขึ้นมาซึ่งเข้าถึงไม่ได้ส่วนที่มีไฟฟ้า L1…

  • ข้อ 3 – วิธีทำความเข้าใจคำจำกัดความของ “อุปกรณ์คลาส I”

    หมายเหตุ ข้อกำหนดนี้รวมถึงตัวนำลงดินป้องกันในสายไฟจากแนวคิดการป้องกันสองชั้น มีข้อควรระวังในการป้องกันไฟฟ้าช็อตอยู่สองประการ ข้อควรระวังประการแรกคือฉนวนพื้นฐาน และข้อควรระวังประการที่สองคือการต่อสายดิน หากฉนวนพื้นฐานล้มเหลว (เช่น การแตกของปลอกสายไฟภายใน หรือความล้มเหลวของฉนวนระหว่างขดลวดและแผ่นสเตเตอร์ในมอเตอร์) กระแสไฟฟ้าที่เป็นอันตรายจะไหลผ่านชิ้นส่วนโลหะที่เข้าถึงได้ เช่น กรอบของเครื่องใช้ไฟฟ้าหรือกรอบหุ้ม ของมอเตอร์พัดลม ดังนั้น หากชิ้นส่วนโลหะต่อสายดิน กระแสไฟฟ้าจะถูกเปลี่ยนเส้นทางผ่านการต่อสายดินและจะไม่ไหลผ่านร่างกายมนุษย์ เนื่องจากความต้านทานระหว่างชิ้นส่วนโลหะที่เข้าถึงได้ของเครื่องกับตัวนำสายดินภายนอกมักจะน้อยมากเมื่อเทียบกับมนุษย์ ร่างกาย. กระแสไฟฟ้าจะไหลผ่านเส้นทางนำไฟฟ้าที่มีความต้านทานต่ำ กล่าวคือ จะถูกเจือจางไปยังโครงข่ายกราวด์ภายนอกผ่านตัวนำกราวด์ ตัวนำสายดินป้องกันในการเดินสายไฟคงที่ของการติดตั้งที่เรากล่าวถึงในที่นี้คือสายดินป้องกันในการเดินสายคงที่ ซึ่งเข้าใจง่ายว่าเป็นช่องเสียบสายดินในเต้ารับไฟฟ้าในบ้านของเรา กระแสไฟฟ้าไหลลงสู่พื้นโลกผ่านทางเต้ารับนี้ โลกเป็นตัวนำที่ดีอันไม่มีที่สิ้นสุด เราสามารถเข้าใจได้ว่าโลกทำให้ประจุเหล่านี้เจือจางลง หรือว่าเรานั้นมีศักยภาพเช่นเดียวกับโลกเพราะเรายืนอยู่บนโลก เฉพาะเมื่อมีความแตกต่างที่อาจเกิดขึ้นในปัจจุบันเท่านั้นที่จะถูกสร้างขึ้น ดังนั้นจะไม่มีกระแสไหลผ่านร่างกายมนุษย์และไม่มีอันตราย ตามชื่อที่แนะนำ ตัวนำสายดินป้องกันใช้สำหรับการป้องกัน ซึ่งเป็นสิ่งที่เรากล่าวถึงข้างต้น เมื่อเกิดอุบัติเหตุการรั่วไหล กระแสไฟฟ้าที่รั่วไหลสามารถส่งลงดินได้ ตัวอย่าง: โดยพื้นฐานแล้ว เครื่องใช้ไฟฟ้าที่มีเปลือกโลหะขนาดใหญ่ได้รับการออกแบบให้เป็นเครื่องใช้ไฟฟ้า Class I เช่น เครื่องปรับอากาศภายนอกอาคาร เตาบาร์บีคิวไฟฟ้า เป็นต้น อย่างไรก็ตาม ผลิตภัณฑ์เครื่องดูดควันบางรุ่นที่มีเปลือกโลหะอาจได้รับการออกแบบให้เป็นเครื่องใช้ไฟฟ้า Class II โดยไม่ต้องต่อสายดิน สายสีเขียวที่แสดงในภาพด้านล่างคือตัวนำกราวด์หรือตัวนำลงดิน และ lt;br หากเครื่องใช้ไฟฟ้าที่มีกล่องโลหะ (เช่น เครื่องปิ้งขนมปัง) มีข้อผิดพลาดโดยที่สายไฟสัมผัสกับกล่องโลหะ…

  • Clause 3 – How to Understand the Definition of “off position”

    off position: stable position of a switching device in which the circuit controlled by the switch is disconnected from its supply or, for electronic disconnection, the circuit is de-energized.NOTE The off position does not imply an all-pole disconnection. With reference to the content in the NOTE, both all-pole disconnection and single-pole disconnection are a stable…